JEHSCU-CM3
 
  JEHSCU0200CM3 JEHSCU0250CM3 JEHSCU0300CM3 JEHSCU0350CM3 JEHSCU0400CM3 JEHSCU0500CM3 JEHSCU0800CM3 JEHSCU0600CM3 JEHSCU0680CM3 JEHSCU1000CM3
Rashladni učin Srednja temperatura R-134a Nom. kW 2.17 (1) 2.48 (1) 3.06 (1) 3.48 (1) 4.24 (1) 5.24 (1) 7.95 (1) 6.16 (1) 6.89 (1) 10.40 (1)
    R-404A Nom. kW 3.49 (1) 4.21 (1) 4.89 (1) 5.50 (1) 6.70 (1) 8.03 (1) 12.95 (1) 9.45 (1) 10.15 (1) 16.45 (1)
    R-407A Nom. kW 3.36 (1) 3.94 (1) 4.54 (1)   6.57 (1) 8.03 (1) 12.55 (1) 9.24 (1) 10.35 (1) 14.75 (1)
    R-407F Nom. kW 3.22 (1) 3.85 (1) 4.45 (1)   6.62 (1) 7.99 (1) 12.65 (1) 9.36 (1) 10.40 (1) 15.95 (1)
Ulazna snaga Srednja temperatura R-134a Nom. kW 1.030 (1) 1.170 (1) 1.460 (1) 1.680 (1) 1.850 (1) 2.300 (1) 3.740 (1) 2.700 (1) 3.150 (1) 4.860 (1)
    R-404A Nom. kW 1.700 (1) 2.040 (1) 2.520 (1) 3.040 (1) 3.330 (1) 4.390 (1) 5.960 (1) 4.920 (1) 5.530 (1) 8.620 (1)
    R-407A Nom. kW 1.630 (1) 2.030 (1) 2.450 (1)   2.970 (1) 3.930 (1) 6.240 (1) 4.620 (1) 5.540 (1) 8.410 (1)
    R-407F Nom. kW 1.780 (1) 2.160 (1) 2.710 (1)   3.210 (1) 4.360 (1) 6.130 (1) 5.030 (1) 5.980 (1) 8.840 (1)
COP Srednja temperatura R-134a 2.12 (1) 2.13 (1) 2.10 (1) 2.08 (1) 2.29 (1) 2.28 (1) 2.13 (1) 2.28 (1) 2.19 (1) 2.14 (1)
    R-404A 2.06 (1) 2.07 (1) 1.94 (1) 1.81 (1) 2.01 (1) 1.83 (1) 2.17 (1) 1.92 (1) 1.84 (1) 1.91 (1)
    R-407A 2.07 (1) 1.95 (1) 1.86 (1)   2.21 (1) 2.04 (1) 2.01 (1) 2.00 (1) 1.87 (1) 1.75 (1)
    R-407F 1.81 (1) 1.79 (1) 1.65 (1)   2.06 (1) 1.83 (1) 2.06 (1) 1.86 (1) 1.74 (1) 1.80 (1)
Godišnja potrošnja električne energije Q R-134a Te -10°C kWh/a           11,969.00 16,741 14,381.00 16,491.00 22,226
  R-404A Te -10°C kWh/a       12,939 14,881.00 18,673.00 27,407 21,344.00 23,536.00 39,372
  R-407A Te -10°C kWh/a         13,054.00 17,546.00 26,747 20,622.00 24,031.00 38,515
  R-407F Te -10°C kWh/a         14,365.00 18,883.00 27,475 21,395.00 24,655.00 38,831
Sezonski omjer energetske učinkovitosti SEPR R-134a Te -10°C           2.69 2.92 2.63 2.57 2.88
  R-404A Te -10°C       2.61 2.77 2.64 2.90 2.72 2.65 2.57
  R-407A Te -10°C         3.09 2.81 2.88 2.75 2.65 2.35
  R-407F Te -10°C         2.83 2.60 2.83 2.69 2.59 2.53
Parametri pri punom opterećenju i temp. okoline 32 °C (točka A) R-134a Te -10°C Nazivni rashladni učin (PA) kW 2.17 2.48 3.06 3.48 4.24 5.24 7.95 6.16 6.89 10.40
      Nazivna ulazna snaga (DA) kW 1.03 1.17 1.46 1.68 1.85 2.30 3.74 2.70 3.15 4.86
      Nazivni COP (COPA) 2.12 2.13 2.10 2.08 2.29 2.28 2.13 2.28 2.19 2.14
  R-404A Te -10°C Nazivni rashladni učin (PA) kW 3.49 4.21 4.89 5.50 6.70 8.03 12.95 9.45 10.15 16.45
      Nazivna ulazna snaga (DA) kW 1.70 2.04 2.52 3.04 3.33 4.39 5.96 4.92 5.53 8.62
      Nazivni COP (COPA) 2.06 2.07 1.94 1.81 2.01 1.83 2.17 1.92 1.84 1.91
  R-407A Te -10°C Nazivni rashladni učin (PA) kW 3.36 3.94 4.54   6.57 8.03 12.55 9.24 10.35 14.75
      Nazivna ulazna snaga (DA) kW 1.63 2.03 2.45   2.97 3.93 6.24 4.62 5.54 8.41
      Nazivni COP (COPA) 2.07 1.95 1.86   2.21 2.04 2.01 2.00 1.87 1.75
  R-407F Te -10°C Nazivni rashladni učin (PA) kW 3.22 3.85 4.45   6.62 7.99 12.65 9.36 10.40 15.95
      Nazivna ulazna snaga (DA) kW 1.78 2.16 2.71   3.21 4.36 6.13 5.03 5.98 8.84
      Nazivni COP (COPA) 1.81 1.79 1.65   2.06 1.83 2.06 1.86 1.74 1.80
Parametri pri punom opterećenju i temp. okoline 25°C R-134a Te -10°C Rashladni učin (P2) kW 2.32 2.65 3.27 3.71 4.58          
      Ulazna snaga (D2) kW 0.91 1.05 1.30 1.51 1.62          
      Deklarirani COP (COP2) 2.55 2.52 2.52 2.46 2.83          
  R-404A Te -10°C Rashladni učin (P2) kW 3.76 4.50 5.23              
      Ulazna snaga (D2) kW 1.54 1.87 2.31              
      Deklarirani COP (COP2) 2.44 2.41 2.26              
  R-407A Te -10°C Rashladni učin (P2) kW 3.61 4.21 4.87              
      Ulazna snaga (D2) kW 1.45 1.82 2.22              
      Deklarirani COP (COP2) 2.50 2.32 2.20              
  R-407F Te -10°C Rashladni učin (P2) kW 3.59 4.25 4.96              
      Ulazna snaga (D2) kW 1.53 1.89 2.37              
      Deklarirani COP (COP2) 2.35 2.25 2.10              
Parametri pri punom opterećenju i temp. okoline 43 °C R-134a Te -10°C Rashladni učin (P3) kW 1.92 2.19 2.72 3.06 3.62 4.51 6.93 5.31 5.99 9.01
      Ulazna snaga (D3) kW 1.23 1.40 1.74 2.02 2.33 2.89 4.56 3.33 3.91 5.92
      Deklarirani COP (COP3) 1.57 1.57 1.57 1.52 1.55 1.56 1.52 1.59 1.53 1.52
  R-404A Te -10°C Rashladni učin (P3) kW 2.73 3.42 3.95 4.26 5.33 6.30 10.40 7.64 8.19 12.65
      Ulazna snaga (D3) kW 2.19 2.52 3.10 3.83 4.16 5.48 7.09 6.00 6.72 10.75
      Deklarirani COP (COP3) 1.25 1.36 1.28 1.11 1.28 1.15 1.47 1.27 1.22 1.18
  R-407A Te -10°C Rashladni učin (P3) kW 2.91 3.47 3.98   5.51 6.77 10.65 7.89    
      Ulazna snaga (D3) kW 1.97 2.39 2.88   3.85 4.86 7.70 5.53    
      Deklarirani COP (COP3) 1.48 1.45 1.38   1.43 1.39 1.38 1.43    
  R-407F Te -10°C Rashladni učin (P3) kW             10.55      
      Ulazna snaga (D3) kW             6.95      
      Deklarirani COP (COP3)             1.52      
Kućište Boja Svjetlo sivo Svjetlo sivo Svjetlo sivo Svjetlo sivo Svjetlo sivo Svjetlo sivo Svjetlo sivo Svjetlo sivo Svjetlo sivo Svjetlo sivo
Dimenzije Jedinica Visina mm 662 662 662 662 872 872 1,727 872 872 1,727
    Širina mm 1,101 1,101 1,101 1,101 1,353 1,353 1,348 1,353 1,353 1,348
    Dubina mm 444 444 444 444 575 575 641 575 575 641
Težina Jedinica kg 70 72 74 74 119 123 218 125 126 218
Ventilator Tip Aksijalni Aksijalni Aksijalni Aksijalni Aksijalni Aksijalni Aksijalni Aksijalni Aksijalni Aksijalni
Radna tvar Tip R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a
  Tip 2 R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A
  Tip 3 R-407A R-407A R-407A   R-407A R-407A R-407A R-407A R-407A R-407A
  Tip 4 R-407F R-407F R-407F   R-407F R-407F R-407F R-407F R-407F R-407F
  GWP 1,430.0 1,430.0 1,430.0 1,430.0 1,430.0 1,430.0 1,430.0 1,430.0 1,430.0 1,430.0
  GWP vrsta 2 3,921.6 3,921.6 3,921.6 3,921.6 3,921.6 3,921.6 3,921.6 3,921.6 3,921.6 3,921.6
  GWP vrsta 3 2,107.0 2,107.0 2,107.0   2,107.0 2,107.0 2,107.0 2,107.0 2,107.0 2,107.0
  GWP vrsta 4 1,825.0 1,825.0 1,825.0   1,825.0 1,825.0 1,825.0 1,825.0 1,825.0 1,825.0
Raspon rada Temperatura okoline Maks. °C         43 43   43 43  
    Min. °C         -20 -20   -20 -20  
Napajanje Faza 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frekvencija Hz 50 50 50 50 50 50 50 50 50 50
  Napon V 400 400 400 400 400 400 400 400 400 400
Napomene   Pogledajte uvjet: Vanjska okolna temperatura = 32°C, temperatura isparavanja = -10°C i 10K pregrijavanje (primjena kod srednjih temperatura) Pogledajte uvjet: Vanjska okolna temperatura = 32°C, temperatura isparavanja = -10°C i 10K pregrijavanje (primjena kod srednjih temperatura) Pogledajte uvjet: Vanjska okolna temperatura = 32°C, temperatura isparavanja = -10°C i 10K pregrijavanje (primjena kod srednjih temperatura) Pogledajte uvjet: Vanjska okolna temperatura = 32°C, temperatura isparavanja = -10°C i 10K pregrijavanje (primjena kod srednjih temperatura) Pogledajte uvjet: Vanjska okolna temperatura = 32°C, temperatura isparavanja = -10°C i 10K pregrijavanje (primjena kod srednjih temperatura) Pogledajte uvjet: Vanjska okolna temperatura = 32°C, temperatura isparavanja = -10°C i 10K pregrijavanje (primjena kod srednjih temperatura) Pogledajte uvjet: Vanjska okolna temperatura = 32°C, temperatura isparavanja = -10°C i 10K pregrijavanje (primjena